TROUBLE
SHOOTING
DISPLAY BLANK, ALARMS DO NOT FUNCTION,
NO POWER TO UNIT
1) Re-check system wiring to insure proper installation
and battery polarity .
2) Check all system fuses and circuit breakers. Before
replacing a blown fuse, locate and correct the cause of the blown fuse.
3) Check the fuse on the DM3. If it is blown, it
indicates that the DM3 probably needs service.
4) Confirm that all system connections are clean and
tight. Particularly check crimp
connections that have been crimped but not soldered as these connections tend
to deteriorate over time.
5) Check the connection from the monitor to the battery.
If possible, check the input voltage to the monitor with a hand held
multi-meter on the "BATTERY" terminals of the monitor.
TO REPLACE THE FUSE ON THE DM3
The fuse is located under the back
panel on the DM3. To remove this panel, remove the two screws securing the back
to the DM3. Lift off the back and you will see the fuse (refer to page 11 for
location). If blown, replace with a new 1 amp type agc fuse. If it blows again,
the DM3 needs service.
ALARMS DO NOT FUNCTION PROPERLY
1) Check alarm calibration. Refer to
Page 10.
2) If using the display on the DM3 to calibrate the
alarms, make sure that all wires are temporarily removed from the CURRENT 2
positions on the terminal block.
INCORRECT CURRENT READINGS
1) Check to be sure that the shunts (internal, and
external, if used) are wired in the negative legs of the system components.
2) Using a digital multimeter, measure the millivolt
reading at the shunt and then at the DM3 terminal block to which it is
connected. Compare this value with the expected current reading and the
displayed value.
3) Check to be sure that the shunts are installed in the
proper location to monitor the desired reading.
4) Check to be sure that there are no alternative paths
around the shunts.
5) If the polarity of the current reading is wrong,
reverse the wires to the internal shunt or the wires going from any external
shunts to the DM3.
RANDOM READINGS ON "CURRENT 2" POSITION
1) Check the connections to the "Shunt" terminals on the
monitor.
2) Electronic "noise" from inverters or other loads can
sometimes influences the readings. Some types of loads (fluorescent lights,
inverters) can generate electronic "noise" that sometimes interferes
with the monitor reading, particularly when sense wires from remote shunts run
close to wiring to the load. Check to
see if strange behavior can be traced to the operation of a certain appliance.
RANDOM READINGS ON "CURRENT 1" POSITION
1)
Check the connections to the "Shunt" terminals on the monitor.
2)
Electronic "noise" from inverters or other loads can sometimes
influence the readings.
CURRENT READINGS INCREASE WHEN THEY SHOULD DECREASE, OR DECREASE WHEN
THEY SHOULD INCREASE
1) Check the location of the shunts in the circuit. Depending upon their
location, they might be reading net current (current in minus current out)
instead of only current in.
CHARGE CURRENT INCREASES WHEN CHARGING STOPS
1) Check the location of the shunt measuring charge current from the
solar panel(s). For correct monitoring, the shunt should be installed in the
negative leg, between the regulator and the battery, not between the solar
panel(s) and the regulator.
CURRENT READINGS LESS THAN EXPECTED
1)
Check to see that modules and batteries are in the correct series-parallel
configuration for proper system voltage and current.
2)
Check for an alternative path to ground around the shunt. .
3)
Make sure that the correct shunt is installed.
4)
Check output from the solar panel(s), and that they are not partially shaded or
dirty.
INCORRECT VOLTAGE READINGS
1) If you have an accurate digital volt meter, check
voltage readings at the battery and at the monitor, to see if they agree.
Voltage drops occur between the regulator and the battery occasionally during
maximum charging. Drops often occur
through old fuses, fuse holders or circuit breaker boxes and at loose or
corroded connections.
If, after reviewing all of the above troubleshooting information, you
cannot get the DM3 to operate properly, it is possible that it may have been
damaged. High voltage from nearby
lightning strikes or unregulated charging sources can damage the monitor. The
built-in lightning protection provides substantial protection, but it is
sometimes overwhelmed. Contact your
installer/dealer to obtain assistance in the troubleshooting of your system.
You may also opt to return the unit to Specialty Concepts for a thorough
check-out.