BENCH TEST PROCEDURE:
SC1
Test equipment
required: Digital Multimeter, Adjustable Power supply
Nominal
Voltage Power Supply Range
12 10-18
Vdc
24 20-36
Vdc
36 30-48
Vdc
48
40-64 Vdc
All
measurements described in this procedure should be made at the controller
terminals.
1) Make sure that
there is a jumper between Battery(+) and Battery Voltage Sense(+) and one
between Battery(-) and Battery Voltage Sense(-).
2) Check continuity
between Battery(-),Solar Panel(-) and Load(-).
3) Turn off the load
circuit breaker and measure the resistance between Load(+) and Battery(+). It
should be open (more than 10M ohm). Turn on the load circuit breaker and re-measure.
It should be less than 0.2 ohm.
4) Measure the
resistance between Solar Panel(+) and Battery(+). It should be open.
5) Set the power
supply to the nominal system voltage. Connect the power supply negative to the
controller Battery(-) terminal. Connect the power supply positive to the
controller Solar Panel(+) terminal. For 36 volt and 48 volt chargers, briefly
connect a jumper between Solar Panel(+) and Battery(+). When the charge mode
light turns on, remove the jumper.
6) Verify that the
charge mode light is on. Measure and note the voltage between Solar Panel(+)
and Solar Panel(-).
7) Measure the
voltage between Battery(+) and Battery(-).
It should be the same as the voltage measured in step 6 to within +/-
0.1 volt. Measure the voltage between Load(+) and Load(-). It should be the
same as the voltage measured in step 6 to within +/- 0.1 volt.
8) Install a jumper
between Battery(+) and Solar Panel(+).
9) Verify the charge
termination and charge resumption set-points by changing the power supply
voltage up and down and observing the activation of the “CHARGE MODE” light.
10) Set the LVD
switch to AUTO LVD. Verify the load disconnect and load reconnect set-points by
changing the power supply voltage up and down and observing the activation of
the load disconnected light. There is a time delay on the load disconnect
circuit. The set-points must be approached slowly to avoid overshooting. With
the controller in the load disconnected mode, press the MANUAL RESET and verify
that the light goes off momentarily. Set the LVD switch to NO LVD and verify
that the load disconnect does not activate.
11) For 12 and 24
volt controllers only; remove the jumper between Battery(+) and Solar Panel(+).
Increase the power supply voltage to 18 volts for a 12 volt system or 36 volts
for a 24 volt system. Measure the voltage between Battery(+) and Battery(-). It
should be about the float voltage.